Flow Sensor Ifm SI0558
IFM CATEGORIES
Flow Sensor SI0558
Brand: Ifm
Product Code: SID10XDBAKOA/US-100
- Consistent monitoring of fluids and gases within pipelines
- Adjustable process connection through the use of adapters
- Simplified adjustment of switch points for rapid configuration
- Durable stainless steel enclosure designed for demanding industrial settings
- LED bar graph for displaying switch point and flow status
Product characteristics
| Total count of inputs and outputs | Count of digital outputs: 1 | ||
| Connection for process | screw connection M18 x 1.5 internal thread | ||
| Media | Fluids; gases | ||
| Intermediate temperature value[°C] | -25...70 | ||
| Pressure classification |
| ||
| Response duration[s] | 1...2; (for a temperature value gradient: 1 K/min) | ||
| Weight[g] | 230.5 | ||
| Housing | cylindrical | ||
| measurements[mm] | Ø 50 / L = 113 | ||
| Substance | stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PC; PBT-GF20; EPDM/X | ||
| Substances (contacted components) | stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A | ||
| Connection for process | screw connection M18 x 1.5 internal thread | ||
| Diameter of probe[mm] | 8.2 | ||
| Setup length IL[mm] | 45 |
Software / programming
| Modification of the switching threshold | tactile switches |
| Surrounding temperature value[°C] | -25...60 |
| Temperature for storage[°C] | -25...100 |
| Safety feature | IP 65; IP 67 |
| Length L of probe[mm] | 45 |
Inputs / outputs
| Total count of inputs and outputs | Count of digital outputs: 1 | ||
| Voltage tolerance for operation[%] | -15...15 | ||
| Voltage for operation[V] | < 24 AC / 18...36 DC; (to SELV/PELV) | ||
| Current draw[mA] | < 80 | ||
| Safety feature rating | III | ||
| Activation delay time[s] | 10 | ||
| Overall count of outputs | 1 | ||
| Output response | output signal | ||
| Count of digital outputs | 1 | ||
| Output feature | typically open | ||
| Contact specifications | 2 A, 24 V AC/DC; (to SELV/PELV) | ||
| Overcurrent protection | no | ||
| Overcurrent protection | no | ||
| Reproducibility[cm/s] | 1...5 | ||
| Comment on repeatability |
| ||
| Temperature variation[cm/s x 1/K] | 0.1; (for water 5...100 cm/s; 10...70 °C) | ||
| Max. temperature value change rate of medium[K/min] | 300 | ||
| Precision of switch points/span>[cm/s] | ± 2...± 10; (for water 5...100 cm/s; 25 °C; default configuration) | ||
| Hysteresis[cm/s] | 2...5; (for water 5...100 cm/s; 25 °C; default configuration) |