Product characteristics

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Measuring span
-0.05...0.4 bar-50...400 mbar-0.725...5.8 psi-5...40 kPa
Connection for process screw connection G 1 with outdoor thread sealing cone
System gold-plated terminals
Sensing element ceramic capacitive force per unit area sensing element
Temperature surveillance no
Application recessed installation compatible for the food and drink sector
Media viscous substances and fluids with suspended particulates; fluids and gases
Intermediate temperature value[°C] -25...150
Minimum force per unit area before bursting
30000 mbar435 psi3000 kPa
Pressure classification
8000 mbar116 psi800 kPa
Vacuum strength
-1000 mbar-0.1 MPa
Kind of force per unit area relative force per unit area
No unused space yes
Damping for the analog output dAA[s] 0...4
Weight[g] 336.8
Housing cylindrical
measurements[mm] Ø 30.2 / L = 122
Substance stainless steel (1.4404 / 316L); PBT
Substances (contacted components) ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface features: Ra < 0.4 / Rz 4; PTFE
Minimum force per unit area cycles 100 million
Fastening torque[Nm] 20
Connection for process screw connection G 1 with outdoor thread sealing cone

Interfaces

communication interface IO-Link
Mode of transmission COM2 (38,4 kBaud)
IO-Link version 1.1
SDCI specification IEC 61131-9
Configurations Digital Measurement Sensor (0x000A), Identification and Diagnostic (0x4000)
SIO mode no
Necessary master port category A
Analog data process 3
Minimum process cycle duration[ms] 3.2
IO-Link force per unit area resolution[mbar] 0.1
IO-Link cyclic process data
Operationbit length
force per unit area16
device status4
IO-Link acyclical functions application-specific label; internal temperature value
Supported DeviceIDs>
Mode of operationDeviceID
default1410
Surrounding temperature value[°C] -25...80
Temperature for storage[°C] -40...100
Safety feature IP 67; IP 68; IP 69K
Measuring span
-0.05...0.4 bar-50...400 mbar-0.725...5.8 psi-5...40 kPa
Analog initiation point
-50...320 mbar-0.725...4.641 psi-5...32 kPa
Analog endpoint
30...400 mbar0.435...5.802 psi3...40 kPa
In increments of
0.1 mbar0.001 psi0.01 kPa
default configuration
ASP = 0.0 barAEP = 400 mbar

Inputs / outputs

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Voltage for operation[V] 18...30 DC
Minimum insulation resistance[MO] 100; (500 V DC)
Safety feature rating III
Reverse polarity safeguard yes
Measuring method hydrostatic
Built-in watchdog yes
Overall count of outputs 2
Output response analog signal; IO-Link; (customizable)
Count of digital outputs 1; (IO-Link)
Total analog outputs 1
Analog current output[mA] 4...20; (expandable)
Max. capacity[O] 700; (Ub = 24 V; (Ub - 9 V) / 21.5 mA)
Short-circuit resistant yes
Overcurrent protection yes
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K; Turn down 1:1)
Characteristics variation[% of the span] < ± 0,2 (DIN EN 61298-2); (incl. zero point and span error, non-linearity, hysteresis; Turn down 1:1)
Linearity variation[% of the span] < ± 0,15; (Turn down 1:1)
Hysteresis variation[% of the span] < ± 0,15; (Turn down 1:1)
Extended stability[% of the span] < ± 0,1; (Turn down 1:1; per year)
Overall deviation across temperature value range
Operating temperature value rangeoverall deviation
-25...15 °CCharacteristics variation ± 0,1 % of the span / 10 K
15...80 °CCharacteristics variation
80...150 °CCharacteristics variation ± 0,15 % of the span / 10 K
Comments on the precision / variation for additional information refer to the section Diagrams and graphs