Pressure Sensor Ifm PN009A


IFM CATEGORIES

Pressure Sensor Ifm pn009a

Pressure Sensor PN009A

Brand: Ifm
Product Code: PN-0-1BRBR14-MFPKG/US/3D /V

  • Suitable for use in hazardous environments
  • With switching output and analog output
  • Easily readable numerical display
  • Durable stainless steel enclosure designed for demanding industrial settings
  • Service life exceeding 100 million force per unit area cycles

Share on:

Product characteristics

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Measuring span
-1...0 bar-1000...0 mbar
Connection for process screw connection G 1/4 with internal threading
System gold-plated terminals
Application for commercial applications
Media fluids and gases
Intermediate temperature value[°C] -20...60
Minimum force per unit area before bursting
30000 mbar3 MPa
Pressure classification
10000 mbar1 MPa
Kind of force per unit area relative force per unit area; vacuum
Programmable delay time dS, dr[s] 0; 0,2...50
Max. response duration for analog output[ms] 3
Weight[g] 304
Housing cylindrical
measurements[mm] Ø 36 / L = 94
Substance stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); polycarbonate (PC); polybutylene terephthalate (PBT); polyetherimide (PEI); fluorocarbon elastomer (FKM); polytetrafluoroethylene (PTFE)
Substances (contacted components) stainless steel (1.4305 / 303); ceramic materials; FKM
Minimum force per unit area cycles 100 million
Connection for process screw connection G 1/4 with internal threading
Integrated restrictor component not available (can be retrofitted)

Software / programming

Modification of the switching threshold Configuration button
Configuration options hysteresis / threshold; typically open / default closed; activation/deactivation delay; damping; display module; current/voltage output
Surrounding temperature value[°C] -20...60
Temperature for storage[°C] -40...100
Safety feature IP 65
Measuring span
-1...0 bar-1000...0 mbar
Setpoint SP[mbar] -990...0
Reset threshold rP[mbar] -995...-5
In increments of[mbar] 5
default configuration
SP1 = -750 mbarrP1 = -770 mbar

Inputs / outputs

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Voltage for operation[V] 18...36 DC; (to SELV/PELV)
Current draw[mA] < 50
Safety feature rating III
Reverse polarity safeguard yes
Voltage surge protection yes; (< 40 V)
Activation delay time[s] 0.3
Built-in watchdog yes
Overall count of outputs 2
Output response output signal; analog output; (customizable)
Electrical engineering design PNP
Count of digital outputs 1
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2
Continuous current rating of the switching output DC[mA] 250
DC switching frequency[Hz] < 170
Total analog outputs 1
Analog current output[mA] 4...20
Max. capacity[O] 500
Analog voltage output[V] 0...10
Minimum load resistance[O] 2000
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Precision of switch points/span>[% of the span] < ± 0,5
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K)
Characteristics variation[% of the span] < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis variation[% of the span] < ± 0,25
Extended stability[% of the span] < ± 0,05; (per 6 months)
Temperature coefficient value for the zero reference[% of the span / 10 K] 0,2; (0...60 °C)
Temperature coefficient value for the range[% of the span / 10 K] 0,2; (0...60 °C)