Pressure Sensor Ifm PN014A


IFM CATEGORIES

Pressure Sensor Ifm pn014a

Pressure Sensor PN014A

Brand: Ifm
Product Code: PN-010-RBR14-QFPKG/US/3D /V

  • Suitable for use in hazardous environments
  • Dual switching outputs, with one that can be set as a diagnostic output
  • Easily readable numerical display
  • Durable stainless steel enclosure designed for demanding industrial settings
  • Service life exceeding 100 million force per unit area cycles

Share on:

Product characteristics

Total count of inputs and outputs Quantity of digital outputs: 2
Measuring span
-1...10 bar-14.5...145 psi-100...1000 kPa-0.1...1 MPa
Connection for process screw connection G 1/4 with internal threading
System gold-plated terminals
Application for commercial applications
Media fluids and gases
Intermediate temperature value[°C] -20...60
Minimum force per unit area before bursting
150 bar2175 psi15 MPa
Pressure classification
75 bar1087 psi7.5 MPa
Kind of force per unit area relative force per unit area; vacuum
Programmable delay time dS, dr[s] 0; 0,2...50

Software / programming

Configuration options hysteresis / range; typically open / default closed; diagnostic function; switching method; switch-on/switch-off delay; damping; display unit
communication interface IO-Link
Mode of transmission COM2 (38,4 kBaud)
IO-Link version 1.1
SDCI specification IEC 61131-9 CDV
Configurations without profile
SIO mode yes
Necessary master port category A
Analog data process 1
Data binary process 2
Minimum process cycle duration[ms] 2.3
Supported DeviceIDs>
Mode of operationDeviceID
default311
Measuring span
-1...10 bar-14.5...145 psi-100...1000 kPa-0.1...1 MPa
Setpoint SP
-0.9...10 bar-12...145 psi-0.09...1 MPa
Reset threshold rP
-0.95...9.95 bar-13...144 psi-0.095...0.995 MPa
In increments of
0.05 bar1 psi0.005 MPa
default configuration
SP1 = 2.50 barrP1 = 2.30 bar
SP2 = 7.50 barrP2 = 7.30 bar

Inputs / outputs

Total count of inputs and outputs Quantity of digital outputs: 2
Voltage for operation[V] 18...36 DC; (to SELV/PELV)
Current draw[mA] < 50
Safety feature rating III
Reverse polarity safeguard yes
Voltage surge protection yes; (< 40 V)
Activation delay time[s] 0.3
Built-in watchdog yes
Overall count of outputs 2
Output response output signal; IO-Link; (customizable)
Electrical engineering design PNP/NPN
Count of digital outputs 2
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2
Continuous current rating of the switching output DC[mA] 250
DC switching frequency[Hz] < 170
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Precision of switch points/span>[% of the span] < ± 0,5
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K)
Characteristics variation[% of the span] < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis variation[% of the span] < ± 0,25
Extended stability[% of the span] < ± 0,05; (per 6 months)
Temperature coefficient value for the zero reference[% of the span / 10 K] 0,2; (0...60 °C)
Temperature coefficient value for the range[% of the span / 10 K] 0,2; (0...60 °C)
Surrounding temperature value[°C] -20...60
Temperature for storage[°C] -40...100
Safety feature IP 65

Download Specification for PN014A

Download PDF

RELATED PRODUCTS