Pressure Sensor Ifm PN3160


IFM CATEGORIES

Pressure Sensor Ifm pn3160

Pressure Sensor PN3160

Brand: Ifm
Product Code: PN-600-SER14-MFRKG/US/ /V

  • Red/green indicator for easy recognition of the acceptable range
  • The process connection is adjustable for optimal alignment
  • Features long-term stability due to robust overload protection
  • Sturdy construction for application in demanding industrial settings

Share on:

Product characteristics

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Measuring span
0...600 bar0...8700 psi0...60 MPa
Connection for process screw connection G 1/4 with internal thread M6 I
System gold-plated terminals
Sensing element metallic thin-film sensor
Application for commercial applications
Media fluids and gases
Intermediate temperature value[°C] -25...80
Minimum force per unit area before bursting
2500 bar36250 psi250 MPa
Pressure classification
800 bar11580 psi80 MPa
Vacuum strength
-1000 mbar-0.1 MPa
Kind of force per unit area relative force per unit area
Response duration[ms] < 3
Programmable delay time dS, dr[s] 0...50
Damping process parameter dAP[s] 0...4
Damping for the analog output dAA[s] 0...4
Max. response duration for analog output[ms] 3

Software / programming

Configuration options hysteresis / threshold; typically open / default closed; activation/deactivation delay; damping; display module; current/voltage output
communication interface IO-Link
Mode of transmission COM2 (38,4 kBaud)
IO-Link version 1.1
SDCI specification IEC 61131-9
SIO mode yes
Necessary master port category A
Analog data process 1
Data binary process 1
Supported DeviceIDs>
Mode of operationDeviceID
Factory configuration / CMPT = 2426
Status_B High Definition / CMPT = 3605
Note
For additional details, please refer to the IODD PDF document in the "Downloads" section
Measuring span
0...600 bar0...8700 psi0...60 MPa

Inputs / outputs

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Voltage for operation[V] 18...30 DC; (to SELV/PELV)
Current draw[mA] < 35
Minimum insulation resistance[MO] 100; (500 V DC)
Safety feature rating III
Reverse polarity safeguard yes
Activation delay time[s] < 0.3
Built-in watchdog yes
Overall count of outputs 2
Output response output signal; analog output; IO-Link; (customizable)
Electrical engineering design PNP
Count of digital outputs 1
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2.5
Continuous current rating of the switching output DC[mA] 150; (200 (...60 °C) 250 (...40 °C))
DC switching frequency[Hz] < 170
Total analog outputs 1
Analog current output[mA] 4...20
Max. capacity[O] 500
Analog voltage output[V] 0...10
Minimum load resistance[O] 2000
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Overcurrent protection yes
Precision of switch points/span>[% of the span] < ± 0,5
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K)
Characteristics variation[% of the span] < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis variation[% of the span] < ± 0,25
Extended stability[% of the span] < ± 0,05; (per 6 months)
Temperature coefficient value for the zero reference[% of the span / 10 K] 0,2; (-25...80 °C)
Temperature coefficient value for the range[% of the span / 10 K] 0,2; (-25...80 °C)
Surrounding temperature value[°C] -25...80
Temperature for storage[°C] -40...100
Safety feature IP 65; IP 67

Download Specification for PN3160