Inductive Sensor Pepperl+Fuchs NBB5-F33X-E2-AMP
Pepperl+Fuchs Categories
Datasheet excerpt: Technical data of NBB5-F33X-E2-AMP
| Overall specifications | ||
|---|---|---|
| transition function | normally open (NO) | |
| Output configuration | PNP | |
| Specified functioning distance | 5 mm | |
| mounting | flush | |
| Output configuration | DC | |
| Guaranteed functioning distance | 0 ... 4.05 mm | |
| diminution factor rAl | 0.25 | |
| diminution factor rCu | 0.2 | |
| diminution factor r304 | 0.6 | |
| diminution factor rBrass | 0.35 | |
| Output configuration | 3-wire | |
| Rated specifications | ||
| Operational voltage | 10 ... 60 V DC | |
| commutation frequency | 0 ... 500 Hz | |
| Deadband | typ. 5 % | |
| Polarity reversal protection | reverse polarity safeguarded | |
| Overcurrent protection | pulsing | |
| voltage loss | = 2.5 V | |
| Operational current | 0 ... 200 mA | |
| Non-conducting current | 0 ... 0.1 mA | |
| No-load input current | = 10 mA | |
| Delay time prior to availability | = 50 ms | |
| State indication for switching | Yellow indicator LED | |
| Parameters related to functional safety | ||
| MTTFd | 1891 a | |
| task duration (TM) | 20 a | |
| Diagnostic Range (DC) | 0 % | |
| Adherence to standards and directives | ||
| Compliance with standards | ||
| Standards | EN IEC 60947-5-2 | |
| Environmental conditions | ||
| Ambient temperature | -35 ... 70 °C (-31 ... 158 °F) | |
| Ambient storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical characteristics | ||
| Linkage method | plug connector, AMP connector Tyco connector housing 1-0967642-1 (A coding) Tyco crimp terminals 0-963726-1 |
|
| Housing material | PBT , black | |
| Protection等级 | IP67 | |
| Measurements | ||
| Height | 10 mm | |
| Width | 25 mm | |
| Length | 73 mm | |
| Note | Fastening torque: 5 Nm | |
Classifications
| Configuration | Classification code |
|---|---|
| ECLASS 13.0 | 27274001 |
| ECLASS 12.0 | 27274001 |
| ECLASS 11.0 | 27270101 |
| ECLASS 10.0.1 | 27270101 |
| ECLASS 9.0 | 27270101 |
| ECLASS 8.0 | 27270101 |
| ECLASS 5.1 | 27270101 |
| ETIM 9.0 | EC002714 |
| ETIM 8.0 | EC002714 |
| ETIM 7.0 | EC002714 |
| ETIM 6.0 | EC002714 |
| ETIM 5.0 | EC002714 |
| UNSPSC 12.1 | 39121550 |
Download Specification for NBB5-F33X-E2-AMP