Inductive Sensor Pepperl+Fuchs NCN2-F56-N1-Y107584
Pepperl+Fuchs Categories
Datasheet excerpt: Technical data of NCN2-F56-N1-Y107584
| Overall specifications | ||
|---|---|---|
| Output configuration | NAMUR | |
| Specified functioning distance | 2 mm | |
| mounting | non-flush | |
| Guaranteed functioning distance | 0 ... 1.62 mm | |
| Actual sensing distance | 1.8 ... 2.2 mm typ. | |
| diminution factor rAl | 0.5 | |
| diminution factor rCu | 0.45 | |
| diminution factor r304 | 0.8 | |
| Output configuration | 2-wire | |
| Rated specifications | ||
| nominal voltage | 8.2 V (Ri approximately 1 kΩ | |
| commutation frequency | 0 ... 300 Hz | |
| Deadband | 1 ... 10 % typ. 3 % | |
| Polarity reversal protection | reverse polarity safeguarded | |
| Current draw | ||
| Measurement plate not found | = 1 mA | |
| Measuring plate identified | = 3 mA | |
| State indication for switching | LED, yellow | |
| Adherence to standards and directives | ||
| Compliance with standards | ||
| Standards | EN IEC 60947-5-2 | |
| Certifications and approvals | ||
| IECEx certification | ||
| Equipment protection rating Gb | IECEx PTB 11.0021X | |
| Equipment protection rating Da | IECEx PTB 11.0021X | |
| Equipment protection rating Mb | IECEx PTB 11.0021X | |
| ATEX certification | ||
| Equipment protection rating Gb | PTB 00 ATEX 2032 X | |
| Equipment protection rating Da | PTB 00 ATEX 2032 X | |
| UL certification | cULus Certified, Standard Use | |
| CML certification | upon request | |
| Environmental conditions | ||
| Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Mechanical characteristics | ||
| Linkage method | cable | |
| Housing material | PA 6 GF35 Grivory GVN-35H sw | |
| detection surface | PA 6 GF35 Grivory GVN-35H sw | |
| Protection等级 | IP67 | |
| Cable | ||
| wire terminal ferrules | yes | |
| Cable thickness | 2.6 mm ± 0.2 mm | |
| Curvature radius | > 10 x cable diameter | |
| Material | PVC | |
| Color | blue | |
| Core count | 2 | |
| cross section of the core | 0.14 mm2 | |
| Length | 0.17 m | |
| Measurements | ||
| Height | 17 mm | |
| Width | 14 mm | |
| Length | 26 mm | |
| Overview information | ||
| Usage in hazardous environments | refer to instruction manuals | |
Classifications
| Configuration | Classification code |
|---|---|
| ECLASS 13.0 | 27274001 |
| ECLASS 12.0 | 27274001 |
| ECLASS 11.0 | 27270101 |
| ECLASS 10.0.1 | 27270101 |
| ECLASS 9.0 | 27270101 |
| ECLASS 8.0 | 27270101 |
| ECLASS 5.1 | 27270101 |
| ETIM 9.0 | EC002714 |
| ETIM 8.0 | EC002714 |
| ETIM 7.0 | EC002714 |
| ETIM 6.0 | EC002714 |
| ETIM 5.0 | EC002714 |
| UNSPSC 12.1 | 39121550 |
Download Specification for NCN2-F56-N1-Y107584