Pressure Sensor Ifm PN4223


IFM CATEGORIES

Pressure Sensor Ifm pn4223

Pressure Sensor PN4223

Brand: Ifm
Product Code: PN-025-RBN14-HFBOW/LS/ /V

  • Isolated Triac output capable of handling currents up to 2.5 A
  • Designed for application in AC power mains
  • Selectable force per unit area units specific to each country
  • Features long-term stability due to robust overload protection

Share on:

Product characteristics

Total count of inputs and outputs Count of digital outputs: 1
Measuring span
0...25 bar0...363 psi0...2.5 MPa
Connection for process screw connection 1/4" NPT with internal thread
Application for commercial applications
Media fluids and gases
Intermediate temperature value[°C] -25...80
Minimum force per unit area before bursting
350 bar5075 psi35 MPa
Pressure classification
100 bar1450 psi10 MPa
Kind of force per unit area relative force per unit area
Programmable delay time dS, dr[s] 0, 0,2,...10, 11,...50
Damping process parameter dAP[s] 0...4
Weight[g] 357.3
Housing cylindrical
measurements[mm] Ø 34 / L = 120
Substance stainless steel (1.4301 / 304); PC; PBT; PA; FKM
Substances (contacted components) stainless steel (1.4305 / 303); ceramic materials; FKM
Minimum force per unit area cycles 100 million
Connection for process screw connection 1/4" NPT with internal thread
Integrated restrictor component not available (can be retrofitted)

Software / programming

Modification of the switching threshold Configuration button
Configuration options hysteresis / band; typically open / default closed; activation/deactivation delay; damping; adjustment of displayed values; display can be rotated and deactivated; display module
Surrounding temperature value[°C] -25...80
Temperature for storage[°C] -40...100
Safety feature IP 65
Measuring span
0...25 bar0...363 psi0...2.5 MPa
Setpoint SP
0.2...25 bar4...363 psi0.02...2.5 MPa
Reset threshold rP
0.1...24.9 bar2...362 psi0.01...2.49 MPa
In increments of
0.1 bar1 psi0.01 MPa

Inputs / outputs

Total count of inputs and outputs Count of digital outputs: 1
Voltage tolerance for operation[%] 5...10
Voltage for operation[V] 90...250 AC
Rated voltage AC[V] < 250
Current draw[mA] < 10
Minimum insulation resistance[MO] 100; (500 V DC)
Safety feature rating II
Reverse polarity safeguard no
Activation delay time[s] 0.2
Built-in watchdog yes
Overall count of outputs 1
Output response output signal
Electrical engineering design Triac
Count of digital outputs 1
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output AC[V] 2
Continuous current rating of the switching output AC[mA] 250; ((...70 °C) 1000 (...60 °C) 1500 (...45 °C) 2500 (...20 °C))
AC switching frequency[Hz] < 160
Short-circuit resistant no
Overcurrent protection no
Precision of switch points/span>[% of the span] < ± 1,0
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K)
Linearity variation[% of the span] < ± 0,5
Hysteresis variation[% of the span] < ± 0,1
Extended stability[% of the span] < ± 0,1; (per year)
Temperature coefficient value for the zero reference[% of the span / 10 K] < ± 0,2; (-25...80 °C)
Temperature coefficient value for the range[% of the span / 10 K] < ± 0,3; (-25...80 °C)

Download Specification for PN4223

Download PDF

RELATED PRODUCTS