Flow Sensor Ifm SD6601


IFM CATEGORIES

Flow Sensor Ifm sd6601

Flow Sensor SD6601

Brand: Ifm
Product Code: SDN12DGXFRKG/US-100

  • Accurate measurement of flow, consumption, force per unit area, and medium temperature value
  • Excellent precision, reproducibility, and measurement responsiveness
  • For the detection of argon (Ar), carbon dioxide (CO2), nitrogen (N2), and pressurized air
  • Red/green indicator for easy recognition of the acceptable range
  • The display can be adjusted for optimal alignment

Share on:

Product characteristics

Total count of inputs and outputs Count of digital outputs: 2; Count of analog outputs: 1
Measuring span
8...2648 scfh0.15...44.15 scfm1...327.4 ft/s
Connection for process screw connection 1/2" NPT with outdoor threading DN15
Application for commercial applications
Media Argon (Ar); carbon dioxide (CO2); nitrogen (N2); pressurized air
Intermediate temperature value[°F] 14...140
Minimum bursting force per unit area[psi] 928
Pressure specification[psi] 232
MAWP (for uses in compliance with CRN)[bar] 9.7
Temperature factor[1/K] ± 0,07 % MW
Precision (within the measurement range) ± (6 % MW + 0,6 % MEW)
Reproducibility ± (0,4 % MW + 0,1 % MEW)
Surrounding temperature value[°F] 32...140
Temperature for storage[°F] -4...185
Max. relative humidity of air[%] 90
Safety feature IP 65; IP 67

Reaction times

Response duration[s] 0.1; (dAP = 0)
Damping process parameter dAP[s] 0...5
Configuration options hysteresis / range; typically open / default closed; current/pulse output; display can be rotated and deactivated; display unit; cumulative counter
Output response output signal; analog output; pulse signal; IO-Link; (customizable)
Electrical engineering design PNP/NPN
Count of digital outputs 2
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2.5
Continuous current rating of the switching output DC[mA] 150; (per output)
Total analog outputs 1
Analog current output[mA] 4...20; (expandable)
Max. capacity[O] 500
Pulse output signal consumption measurement device
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Overcurrent protection yes

Inputs / outputs

Total count of inputs and outputs Count of digital outputs: 2; Count of analog outputs: 1
Voltage for operation[V] 18...30 DC; (to SELV/PELV)
Current draw[mA] < 80
Safety feature rating III
Reverse polarity safeguard yes
Activation delay time[s] 1
Inputs reset function
Measuring span
8...2648 scfh0.15...44.15 scfm1...327.4 ft/s
Show range
0...3178 scfh0...52.95 scfm0...393 ft/s
Definition of detail level
2 scfh0.05 scfm0.2 ft/s
Setpoint SP
23...2648 scfh0.38...44.13 scfm2.8...327.3 ft/s
Reset threshold rP
10...2635 scfh0.16...43.91 scfm1.2...325.7 ft/s
Analog initiation point ASP
0...2119 scfh0...35.31 scfm0...261.9 ft/s
Analog endpoint AEP
530...2649 scfh8.83...44.14 scfm65.5...327.4 ft/s
Minimal flow termination LFC
3...28 scfh0.05...0.47 scfm0.4...3.5 ft/s
In increments of
1 scfh0.01 scfm0.1 ft/s
communication interface IO-Link
Mode of transmission COM2 (38,4 kBaud)
IO-Link version 1.1
SDCI specification IEC 61131-9 CDV
Configurations Digital Measurement Sensor (0x800A), Identification and Diagnostics (0x4000)
SIO mode yes
Necessary master port category A
Analog data process 8
Data binary process 2
Minimum process cycle duration[ms] 7.2
Supported DeviceIDs>
Mode of operationDeviceID
default865

Download Specification for SD6601

Download PDF