Flow Sensor Ifm SI0553


IFM CATEGORIES

Flow Sensor Ifm si0553

Flow Sensor SI0553

Brand: Ifm
Product Code: SID10ADHFPKG/US-100

  • Consistent monitoring of fluids and gases within pipelines
  • Adjustable process connection through the use of adapters
  • Simplified adjustment of switch points for rapid configuration
  • Durable stainless steel enclosure designed for demanding industrial settings
  • LED bar graph for displaying switch point and flow status

Share on:

Product characteristics

Total count of inputs and outputs Count of digital outputs: 1
Connection for process screw connection M18 x 1.5 internal thread
Media Fluids; gases; corrosive substances
Intermediate temperature value[°C] -25...80
Pressure classification
300 bar30 MPa
Response duration[s] 1...2; (for a temperature value gradient: 1 K/min)
Weight[g] 244
Housing cylindrical
measurements[mm] Ø 50 / L = 113
Substance stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PC; PBT-GF20; EPDM/X
Substances (contacted components) Hastelloy C-4 (2.4610); O-ring: FKM 80 Shore A
Connection for process screw connection M18 x 1.5 internal thread
Diameter of probe[mm] 8.2
Setup length IL[mm] 45

Software / programming

Modification of the switching threshold tactile switches
Surrounding temperature value[°C] -25...80
Temperature for storage[°C] -25...100
Safety feature IP 67
Length L of probe[mm] 45

Inputs / outputs

Total count of inputs and outputs Count of digital outputs: 1
Voltage for operation[V] 19...36 DC
Current draw[mA] < 60
Safety feature rating III
Reverse polarity safeguard yes
Activation delay time[s] 10
Overall count of outputs 1
Output response output signal
Electrical engineering design PNP
Count of digital outputs 1
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2.5
Continuous current rating of the switching output DC[mA] 250
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Overcurrent protection yes
Reproducibility[cm/s] 1...5
Comment on repeatability
for water 5...100 cm/s; 25 °C
default configuration
Temperature variation[cm/s x 1/K] 0.1; (for water 5...100 cm/s; 10...70 °C)
Max. temperature value change rate of medium[K/min] 300
Precision of switch points/span>[cm/s] ± 2...± 10; (for water 5...100 cm/s; 25 °C; default configuration)
Hysteresis[cm/s] 2...5; (for water 5...100 cm/s; 25 °C; default configuration)

Download Specification for SI0553

Download PDF