Flow Sensor Ifm SM9400


IFM CATEGORIES

Flow Sensor Ifm sm9400

Flow Sensor SM9400

Brand: Ifm
Product Code: SMK32XGXFRKG/US-100

  • Accurate monitoring of flow, consumption, and medium temperature value
  • Excellent precision, reproducibility, and measurement responsiveness
  • Featuring switching output, analog output, and pulse output
  • Easily readable numerical display

Share on:

Product characteristics

Total count of inputs and outputs Count of digital outputs: 2; Count of analog outputs: 1
Measuring span
5...300 l/min0.3...18 m³/h
Connection for process screw connection Rc 1 1/2 internal thread DN40
System gold-plated terminals
Application Cumulative function; detection of empty pipeline; intended for industrial use
Media Conductive fluids; water; aqueous media
Comment on medium
conductivity: = 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Intermediate temperature value[°C] -10...90
Pressure classification
16 bar1.6 MPa
Precision (within the measurement range) ± (0,8 % MW + 0,5 % MEW)
Reproducibility ± 0,2% MEW
Surrounding temperature value[°C] -10...60
Temperature for storage[°C] -25...80
Safety feature IP 65; IP 67

Reaction times

Response duration[s] 0.35; (dAP = 0)
Programmable delay time dS, dr[s] 0...50
Damping process parameter dAP[s] 0...5
Configuration options Flow supervision; volume meter; preset counter; temperature value monitoring; hysteresis / window; typically open / closed; switching logic; current/voltage/frequency/pulse output; startup delay; display can be turned off; display unit; empty pipe detection
Overall count of outputs 2
Output response output signal; analog output; pulse signal; frequency signal; IO-Link; (customizable)
Electrical engineering design PNP/NPN
Count of digital outputs 2
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2
Continuous current rating of the switching output DC[mA] 250; (per output)
Total analog outputs 1
Analog current output[mA] 4...20; (expandable)
Max. capacity[O] 500
Analog voltage output[V] 0...10; (adjustable)
Minimum load resistance[O] 2000
Pulse output signal flow measurement device
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Overcurrent protection yes
Output frequency[Hz] 0.1...10000

Inputs / outputs

Total count of inputs and outputs Count of digital outputs: 2; Count of analog outputs: 1
Voltage for operation[V] 18...32 DC; (to SELV/PELV)
Current draw[mA] < 150
Safety feature rating III
Reverse polarity safeguard yes
Activation delay time[s] 5
Measuring method magnetic-induction
Inputs reset function
Measuring span
5...300 l/min0.3...18 m³/h
Show range
-360...360 l/min-21.6...21.6 m³/h
Definition of detail level
0.5 l/min0.02 m³/h
Setpoint SP
6.5...300 l/min0.4...18 m³/h
Reset threshold rP
5...298.5 l/min0.3...17.9 m³/h
Analog initiation point ASP
0...240 l/min0...14.4 m³/h
Analog endpoint AEP
60...300 l/min3.6...18 m³/h
Minimal flow termination LFC
< 15 l/min< 0.9 m³/h
In increments of
0.5 l/min0.02 m³/h
Measurement dynamics 1:60
communication interface IO-Link
Mode of transmission COM2 (38,4 kBaud)
IO-Link version 1.1
SDCI specification IEC 61131-9 CDV
Configurations Intelligent Sensor: Data Process Variable; Device Identification
SIO mode yes
Necessary master port category A
Analog data process 3
Data binary process 2
Minimum process cycle duration[ms] 5
Supported DeviceIDs>
Mode of operationDeviceID
default391

Download Specification for SM9400