Level Sensor Ifm LT3022
IFM CATEGORIES
Level Sensor LT3022
Brand: Ifm
Product Code: LT0264B-B-00KLPKG/US
- Consistent level detection in tanks and containers
- Designed for application with water, oils, and cooling fluids
- Intuitive configuration of switching function and switch thresholds
- Combined level and temperature value monitoring within a single unit
- Easily readable numerical display
Product characteristics
| Total count of inputs and outputs | Total digital outputs: 1; Total analog outputs: 1 | ||
| default configuration | mineral-based oils | ||
| Length L of probe[mm] | 264 | ||
| Media | aqueous coolants; oils; oil-based fluids; water; substances akin to water | ||
| Dielectric permittivity of the medium | > 2 | ||
| Not suitable for | highly conductive substances; adhesive media; granules; bulk materials; acids; alkalines | ||
| Pressure in the tank |
| ||
| Configuration options | hysteresis / range; typically open / default closed; switching configuration; current/voltage output; SP/rP location; OP adjustment; medium choice; offset adjustment; activation/deactivation delay | ||
| Weight[g] | 290 | ||
| measurements[mm] | Ø 16 | ||
| Substance | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); fluorocarbon elastomer (FKM); nitrile butadiene rubber (NBR); polybutylene terephthalate (PBT); polycarbonate (PC); polyamide (PA); polypropylene (PP); thermoplastic vulcanizate (TPV) | ||
| Substances (contacted components) | PP |
Interfaces
| communication interface | IO-Link | ||||
| Mode of transmission | COM2 (38,4 kBaud) | ||||
| IO-Link version | 1.1 | ||||
| SDCI specification | IEC 61131-9 | ||||
| Configurations | Intelligent Sensor: Data Process Variable; Device Identification; Device Diagnosis | ||||
| SIO mode | yes | ||||
| Necessary master port category | A | ||||
| Analog data process | 4 | ||||
| Data binary process | 1 | ||||
| Minimum process cycle duration[ms] | 4.5 | ||||
| Supported DeviceIDs |
| ||||
| Surrounding temperature value[°C] | 0...60 | ||||
| Temperature for storage[°C] | -25...80 | ||||
| Safety feature | IP 67 | ||||
| default configuration | mineral-based oils | ||||
| Length L of probe[mm] | 264 | ||||
| Operating range A[mm] | 195 | ||||
| Non-active range I1 / I2[mm] | 53 / 16 |
Inputs / outputs
| Total count of inputs and outputs | Total digital outputs: 1; Total analog outputs: 1 |
| Voltage for operation[V] | 18...30 DC |
| Current draw[mA] | < 50 |
| Safety feature rating | III |
| Reverse polarity safeguard | yes |
| Activation delay time[s] | < 3 |
| Overall count of outputs | 2 |
| Output response | output signal; analog output; IO-Link |
| Electrical engineering design | PNP/NPN |
| Count of digital outputs | 1 |
| Output feature | typically open / closed; (customizable) |
| Max. voltage drop at switching output DC[V] | 2.5 |
| Continuous current rating of the switching output DC[mA] | 200 |
| Total analog outputs | 1 |
| Analog current output[mA] | 4...20, invertible |
| Max. capacity[O] | 500 |
| Analog voltage output[V] | 0...10, reversible |
| Minimum load resistance[O] | 2000 |
| Overcurrent protection | yes |
| Method of overcurrent protection | thermal, pulsed mode |
| Overcurrent protection | yes |
| Measurement error[% of the final value] | ± 5 |
| Reproducibility | ± 2 |
| Definition of detail level[mm] | 5 |
| Zero voltage signal[V] | 0 |
| Zero current signal[mA] | 4.0 |
| Complete signal (voltage)[V] | 10 |
| Complete signal (current)[mA] | 20 |
Download Specification for LT3022