Product characteristics

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Measuring span
-0.0124...0.25 bar-12.4...250 mbar-5...100.4 inH2O-1.24...25 kPa
Connection for process screw connection G 1 with outdoor thread sealing cone
System gold-plated terminals
Application food and drink sector
Setup Housing with 350° rotational freedom
Media viscous substances and fluids with suspended particulates; fluids and gases
Intermediate temperature value[°C] -20...60; (when utilized beyond the hazardous zone:; Surrounding temperature value: -25...85 °C; Intermediate temperature value: -25...125 °C / 145 °C < 1h)
Minimum force per unit area before bursting
30000 mbar12044 inH2O3000 kPa
Pressure classification
6000 mbar2400 inH2O600 kPa
Kind of force per unit area relative force per unit area; vacuum
Response duration[ms] < 100
Damping process parameter dAP[s] 0.1...100
Damping for the analog output dAA[s] 0.1...100
Step response duration for analog output[ms] 25
Weight[g] 509
Housing cylindrical
measurements[mm] Ø 36 / L = 132
Substance stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE
Substances (contacted components) ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); stainless steel (1.4404 / 316L); surface properties: Ra < 0.4 / Rz 4; PTFE; EPDM
Minimum force per unit area cycles 100 million
Connection for process screw connection G 1 with outdoor thread sealing cone

Software / programming

Configuration options hysteresis / range; typically open / default closed; switching method; current/voltage output; damping; adjustment of displayed values; display can be rotated and deactivated; display module; zero point; span
Surrounding temperature value[°C] -20...60
Temperature for storage[°C] -40...100
Safety feature IP 65
Measuring span
-0.0124...0.25 bar-12.4...250 mbar-5...100.4 inH2O-1.24...25 kPa
Setpoint SP
-12...250 mbar-4.8...100.4 inH2O-1.2...25 kPa
Reset threshold rP
-12.4...249.6 mbar-5...100.2 inH2O-1.24...24.96 kPa
Analog initiation point
-12.4...187.4 mbar-5...75.2 inH2O-1.24...18.74 kPa
Analog endpoint
50...250 mbar20.1...100.4 inH2O5...25 kPa
In increments of
0.2 mbar0.1 inH2O0.02 kPa

Inputs / outputs

Total count of inputs and outputs Total digital outputs: 1; Total analog outputs: 1
Voltage for operation[V] 18...32 DC
Current draw[mA] < 50
Safety feature rating III
Reverse polarity safeguard yes
Activation delay time[s] 0.5
Measuring method hydrostatic
Built-in watchdog yes
Overall count of outputs 2
Output response output signal; analog output; (customizable)
Electrical engineering design PNP/NPN
Count of digital outputs 1
Output feature typically open / closed; (customizable)
Max. voltage drop at switching output DC[V] 2
Continuous current rating of the switching output DC[mA] 250
DC switching frequency[Hz] 6
Total analog outputs 1
Analog current output[mA] 4...20, invertible; (expandable 1:4)
Max. capacity[O] (Ub - 10 V) / 20 mA
Analog voltage output[V] 0...10, reversible; (adjustable 1:4)
Minimum load resistance[O] 2000
Overcurrent protection yes
Method of overcurrent protection yes (momentary)
Overcurrent protection yes
Precision of switch points/span>[% of the span] < ± 0,2; (Turn down 1:1)
Reproducibility[% of the span] < ± 0,1; (with temperature value fluctuations < 10 K; Turn down 1:1)
Characteristics variation[% of the span] < ± 0,2; (Turn down 1:1 , linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1)
Linearity variation[% of the span] < ± 0,15; (Turn down 1:1)
Hysteresis variation[% of the span] < ± 0,15; (Turn down 1:1)
Extended stability[% of the span] < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient value for the zero reference[% of the span / 10 K] < ± 0,05; (0...70 °C)
Temperature coefficient value for the range[% of the span / 10 K] < ± 0,15; (0...70 °C)